Solutions & flagship projects

Humidity control for pharmaceutical cleanrooms

Many drug-manufacturing steps need lower and more stable humidity than ordinary air-conditioning can reach: granulation, tableting, encapsulation, film coating and especially effervescent tablets and hygroscopic powders. Air-conditioning only brings a room to about 50–60 %RH; going lower and holding it to the GMP file requires a DryMax desiccant dehumidifier or a DryMax DMTH unit treating temperature and humidity together. ENCO has built humidity control for pharmaceutical production rooms since 1997 (a 20 °C / 20 %RH project with a −3.2 °C dew point), installed DMTH units in an effervescent-tablet plant and HARISON dehumidifiers in medicine warehouses.

Wrong humidity makes powders cake, tablets stick to punches, soft capsules deform, effervescent tablets react early and validation fails. Each area of a pharmaceutical plant needs its own humidity level.

Technical content byThS. Nguyễn Minh Thái · Updated

What moisture causes

  • Powders and granules absorb moisture, cake and flow poorly at tableting
  • Effervescent tablets and hygroscopic powders react or lose shelf life
  • Tablets stick to punches, uneven film coating, soft capsules deform
  • Humidity swings and failed GMP validation records

Conditions to hold

According to each plant's GMP file. Reference: effervescent and hygroscopic-powder areas may need down to 20 °C / 20 %RH (ENCO project); pharmaceutical stores usually 30–45 %RH.

Reference values. ENCO engineers calculate to the requirements and actual moisture load of each site.

ENCO's solution

  • Survey and moisture-load calculation for each cleanroom against the plant's GMP file
  • DryMax desiccant dehumidifiers or DryMax DMTH units (temperature + humidity) connected to the existing cleanroom AHUs
  • HARISON dehumidifiers for raw-material and finished-goods stores
  • Warranty and scheduled maintenance; data support for validation files

By area and process

AreaConditions and risksHow ENCO handles it
Dispensing, granulation, dryingPowders and granules absorb moisture and cakeDry air from a DryMax desiccant unit fed into the cleanroom AHU
Tableting, encapsulationTablets stick, soft capsules deformDryMax DMTH unit holding temperature and humidity together
Effervescent tablets, hygroscopic powdersHumidity must be very low, down to 20 %RHDryMax desiccant dehumidifier controlled on dew point
Film coating, blister and bottle packingUneven coating; tablets absorb moisture before sealingStable room conditions per the file, monitored by data loggers
Raw-material and finished-goods stores'Nồm' season pushes humidity above GSP limitsHARISON industrial dehumidifiers placed along rack rows

Typical equipment

Featured projects

See all engineering activities →

Selected ENCO installations

DateProvinceWork
10/2025HanoiCommissioning a DryMax unit for a pharmaceutical production room
08/2025Ho Chi Minh CityHARISON HD-504B dehumidifiers for a pharmaceutical warehouse
07/2025HanoiDryMax DM-810 desiccant dehumidifier for a pharmaceutical laboratory
05/2025HanoiWarranty service on a DryMax DMTH-8 unit in a pharmaceutical production room
03/2025HanoiHARISON HD-504PS dehumidifiers for a high-bay medicine warehouse

From ENCO service records; customer names are not disclosed.

FAQ

What humidity does a pharmaceutical cleanroom need?

It depends on the process and the plant's GMP file. Effervescent and hygroscopic-powder areas may need down to 20 °C / 20 %RH; tableting and encapsulation rooms are usually below what air-conditioning can reach; pharmaceutical stores usually 30–45 %RH. ENCO engineers calculate to each room's specific requirement.

Can air conditioning bring humidity down to 20 %RH?

No. Ordinary air conditioning brings humidity to about 50–60 %RH; lower levels need a desiccant rotor dehumidifier.

How does DMTH differ from DM?

The DM series only dehumidifies; DMTH has an integrated cooling coil so it handles both temperature and humidity in one unit.

What information does ENCO need to quote for a pharmaceutical cleanroom?

Layout drawings and cleanliness class of each room, the temperature and humidity required in the GMP file, fresh-air and supply airflow of the existing AHUs, number of workers and the products made. ENCO engineers survey free of charge.

Ask ENCO engineers to design a solution for your site

Send the room size, target humidity and the goods stored; ENCO surveys and proposes a solution free of charge.